Dielectric fluids

Nine grades. One molecule team.

Runhe designs its own molecular structures, so viscosity, dielectric strength and boiling behaviour are tuned for the system — not chosen from a catalogue.

Dielectric coolant
Portfolio

Technical data

Viscosity in cSt, dielectric strength in kV/2.5 mm, flash point in °C (closed cup), thermal conductivity in W/mK.

Product codeChemical component Viscosity 25 °C
cSt
Viscosity 40 °C
cSt
Breakdown strength
kV/2.5 mm
Flash point
°C
Thermal conductivity
W/mK
Dielectric constantTypical application
PCT-5Modified polysiloxane5 ± 13 ± 1> 30> 1250.152.5Cold plate · data center, NEV
PCT-10Modified polysiloxane10 ± 18 ± 1> 30> 1750.162.6Cold plate · data center
PCL-10Hydrocarbon synthetic oil10 ± 18 ± 1> 40> 1900.152.0Cold plate · data center
PCL-15Hydrocarbon synthetic oil15 ± 112 ± 1> 50> 1650.152.2Cold plate · data center
PCM-10Modified polysiloxane10 ± 18 ± 1> 50> 1850.162.6Immersion · data center
PCM-14Modified polysiloxane14 ± 210 ± 1> 50> 1900.142.4Immersion · data center, storage
PCM-20Modified polysiloxane25 ± 218 ± 2> 35> 2300.152.6Immersion · energy storage
PCM-150Modified polysiloxane150 ± 15115 ± 15> 35> 3000.152.6Immersion · energy storage, charging
PCF-5Fluorine-based coolant1.20.9> 20—0.072.2Two-phase immersion · AI data center

Swipe the table sideways to see every column.

Values from the Runhe liquid cooling manual. Application notes are typical rather than exclusive — confirm the grade with our engineers for a specific system.

Cold plate

PCT & PCL

Excellent anti-corrosion behaviour and long-term stability for closed loops. PCT is polysiloxane-based; PCL is a hydrocarbon synthetic oil.

Single-phase immersion

PCM series

High thermal conductivity, low dielectric constant and a wide operating temperature range. Kinematic viscosity at −30 °C is roughly one quarter that of competing fluids.

Two-phase immersion

PCF-5

A fluorinated liquid with outstanding electrical insulation, chemical inertness and thermal stability — the fluid behind the RH-ALIM-8 cabinet.

Selection guide

Match the fluid to the workload.

01

Single-phase immersion

Ideal for conventional high-power-density data centers. Simple system architecture, easy maintenance, and the lowest operational complexity.

02

Two-phase immersion

Designed for ultra-high-power-density AI computing. Higher cooling limit per litre of fluid, at the cost of a sealed, pressure-managed system.

03

Cold plate

Best for retrofitting existing data centers and for new builds with standard racks. Low retrofit cost and fast deployment.

Our technical team can provide customised coolant formulations and complete system solutions based on your specific requirements.

Compatibility

Tested against the hardware, not just the datasheet.

All Runhe coolants pass rigorous compatibility testing and are fully compatible with mainstream server components — seals, PCBs, cables, connectors and GPUs — so the whole system stays stable over time.

  • Elastomer and seal swell testing
  • PCB and connector immersion testing
  • Long-duration thermal and electrical stability
Server board

Send us the loop, we will name the fluid.

Tell us the hardware, the supply temperature and the maintenance interval you need. We will recommend a grade and a top-up strategy.